We Will Understand this Formula by a Simple Calculation
A Temperature Transmitter Range is 0 to 50 c is connected to an PLC analig input card . the PLC analog input Card row count Starting from 7250 for 4 mA ANF 33208 For 20 mA. A PLC reading is 17975 row count and Calculate Transmitter Actual Reading.
We Know That
Given
Data @4Ma = 7250
Data @20 Ma = 33208
Range of Transmitter = 0 to 50 c
Resolution :- 0.1
Data Offset = 7250
Data Span = 33208 – 7250
= 25958
EU Offset = 0 x 10 = 0
EU Span = (60-0) x10
= 600
Data = 17975
EU = ((EUSpan
x (DATA – DataOffset))/DataSpan) + EUOffset
EU= ((600 X (17975-
7250)) / 25958 + 0
EU= ((600 X
(10725)) /25958
EU =
(6435000)/25958
EU= 247
Process Value
= EU/ Factor
Process Value
= 247/10= 24.7 c